eFlo 2.0 Electronic Flow Meter

eFlo 2.0 is SSi’s newest  electronic flow measurement instrument. Like our previous eFlo models, the 2.0 offers simple compatibility with existing controls, making tracking and monitoring gas flows easier than ever. Designed for use in the harshest industrial environments, eFlo allows for easy replacement of manual flow meters and seamlessly integrates into existing control systems.

NOTE: eFlo 2.0 replaces eFlo 1.5.  However, SSi continues to provide service and parts for eFlo 1.5.  Documentation is available here.

Features and Benefits

Integrated communication via Modbus over RS485 (RTU) and Ethernet (TCP)
Pressure and temperature compensation for precise flow calculation
Flow Meter View software and mobile interface for configuration
Available with electronic valve, with or without control
Analog control and feedback for data acquisition
Direct and remote setpoint control
Built-in high/low flow alarms
Flow Totalizing
Compact footprint
Onboard datalogging
NIST-traceable calibration
Precision flow mesaurment
USB configuration tools
Mobile-friendly and web-based remote configuration
Flow calibration can be certified in use for CQI-9 requirements
Digital display: easy-to-use touch pad and optional touchscreen
SCADA integration: Current Flow, Totalized Flow, Setpoint, Cost Calculation
1 1/4" NPT

Supported Gases


AcetyleneHelium
AirHydrogen
AmmoniaHydrogen Chloride
ArgonHydrogen Sulfide
ButaneMethane
Carbon DioxideNatural Gas
Carbon MonoxideNeon
ChlorineNitrogen
Dissociated AmmoniaNitrous Oxide
Endothermic Gas (C3H8)Oxygen
Endothermic Gas (CH4)Propane
EthaneSulfur Dioxide
EthyleneOther (Contact SSi)
Exothermic Gas

Power Required:24VDC @ 400mA
Accuracy:±4%
Turndown Ratio:6:1
Gas Temp. Limits:32°F to 150°F (0°C to 65.6°C)
Ambient Temp. Limits:32°F to 150°F (0°C to 65.6°C)
Flow Output Signal (Linear):4-20mA
Max. Output Signal Load:500Ω
Input Control Signal (Linear):4-20mA
Response Time:1 - 10 seconds
Communications:RS485, Ethernet, USB
Communications Protocol:Modbus RTU, Modbus TCP
Flow Meter Pressure Limits:5 psig max.
Pipe Fitting1 1/4" NPT

    Your Name (required)


    Company (required):


    Phone (required):


    Your Email (required):


    Address (required):


    City, State, Zip (required):


    Country (required):


    I'm a (required):


    Notes:




    Flow Meters

    (Q26) What do the alarm codes mean on my eFlo?

    Alarm CodePossible CausesPossible Corrective Actions
    LoPr - Low PressureActivated when low pressure has been indicated based on either factory or user specified values

    *factory values are not editable and cannot be deactivated; call SSI with any questions

    • Increase regulator pressure

    • Verify all upstream solenoids and/or ball valves are open

    *make sure not to exceed pressure limits for the sensors indicated on page 6
    hiPr- High PressureActivated when high pressure has been indicated based on either factory or user specified values

    If indicated pressure is above the range of the sensor, the meter WILL NOT show accurate values

    *factory values are not editable and cannot be deactivated; call SSI with any questions
    Decrease regulator pressure below the usable range of the sensors

    *make sure not to exceed pressure limits for the sensors indicated on page 6
    LofL- Low FlowActivated when low flow has been indicated based on user specified values

    • Increase flow rate on meter to a value above what has been set

    • It is possible that low pressure is limiting the flow rate and pressure should be increased

    • It is also possible that high pressure has been achieved and the meter is now reading incorrectly

    hiFL - High FlowActivated when high flow has been indicated based on user specified values

    • Increase flow rate on meter to a value above what has been set

    • It is possible that low pressure is limiting the flow rate and pressure should be increased